Done shopping? You can create a PDF of your cart for later or for your purchasing dept! Details at checkout.
Hear What Our Customers Are Saying
-
20+ Years Experience Helping IT Heroes
Take advantage of 20+ years of expertise from a partner with available resources for large deployments, multi-site projects, and complex IT initiatives. We have the team to get the job done. -
Free Solution Design With White Glove Engineers
Solutions architects and project engineers will help you envision a successful outcome and give you personalized recommendations based on your unique needs. Free. Apply today. -
Configuration & Installation Services
Let us take care of configuring and installing your equipment so you can get back to business. Available nationwide. Apply today. -
Equipment Trade-In Program
Refreshing old hardware? Let us coordinate the recycling or destruction in an environmentally friendly and safe manner. As a bonus, working with us gives you access to specific trade-in discounts towards your network refresh. Apply today. -
Exclusive Incentives, Special Pricing, & Financing
After helping you build and validate your solution, we’ll include any applicable discounts, financing, and incentives applied to your project to guarantee you get the most value out of your IT investments through Hummingbird Networks. Apply today.
1500VA UPS Smart Pro Tower Line-Interactive 8 outlet w/ SNMP Slot
Key Features
- SMART 1500SLT line-interactive UPS offers battery derived sine wave AC output during power outages, voltage regulation during brownouts and overvoltages, plus network-grade AC surge suppression
- 1500VA/900 watt power handling capability with full-time sine wave output offers guaranteed compatibility with networking, telecom and other sensitive electronic devices
- Large internal batteries offer runtimes of 17 minutes at half load (750VA/450 watts) and 6 minutes at full load (1500VA/900 watts)
- Automatic Voltage Regulation (AVR) circuits maintain user-selectable 100, 110, 120 or 127V nominal output over an input voltage range of 91 to 145V
- Includes 8 fully-protected NEMA 5-15R output receptacles arranged in a single load bank that can be powered off and back on again via software interface
- PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, pager & email notification, event logging and running user-defined script commands
- Offers simultaneous monitoring by up to 3 directly-connected devices through included USB, DB9 and SNMP* interfaces (*requires optional SNMPWEBCARD), or the monitoring of any number of additional UPS systems over IP with included PowerAlert monitoring software.
- Communications ports support messaging of UPS and line power status, including on-battery, low-battery, power restored, AC line voltage, DC battery voltage and remaining battery capacity
- Supports timed inverter shutoff after unattended shutdown, activate self-test and UPS output power control for scheduled or immediate reboot of connected equipment
- Supports Tripp Lite's WatchDog software application to restore unresponsive programs by systematically restarting applications, operating systems and ultimately rebooting completely locked computers by momentarily switching UPS power off and back on again (requires optional WATCHDOGSW)
- LEDs offer continuous detailed status information of UPS operating parameters and site power quality
- Hot-swappable batteries allow on-site battery replacement without powering off connected equipment
Package Includes
- SMART 1500SLT UPS System
- PowerAlert Software CD-Rom
- USB and serial cabling
OUTPUT | |
Output Volt Amp Capacity (VA) | 1500 |
Output kVA capacity (kVA) | 1.5 |
Output Watt Capacity (watts) | 900 |
Output power factor | 14:24 |
Nominal Output Voltage(s) Supported | 100V; 110V; 120V |
Nominal Voltage details | 120V default (voltage selection via back panel switches) |
Frequency compatibility | 50 / 60 Hz |
Output voltage regulation (line mode) | -13%, + 15% |
Output voltage regulation (Battery mode) | +/- 5% |
Built-in UPS output receptacles | 8 5-15R outlet(s) |
Output AC waveform (AC mode) | Sine wave |
Output AC waveform (battery mode) | Pure Sine wave |
INPUT | |
Rated input current (at maximum load) | 10.1A (100V), 9.3A (110V), 8.6A (120V) |
Nominal Input Voltage(s) Supported | 100V AC; 110V AC; 120V AC |
UPS input connection type | 5-15P |
UPS Input cord length (ft.) | 6 |
UPS Input cord length (m) | 1.8 |
Recommended Electrical Service | 15A 120V |
Phase | Single-Phase |
BATTERY | |
Full load runtime (minutes) | 8 min. (900w) |
Half load runtime (minutes) | 20 min. (450w) |
DC system voltage (VDC) | 36 |
Battery recharge rate (included batteries) | Less than 8 hours from 10% to 90% |
Replacement battery cartridge (internal UPS battery replacement) | RBC36-SLT |
Battery Access | Battery access door |
Battery replacement description | Hot-swappable, user replaceable batteries |
VOLTAGE REGULATION | |
Voltage regulation description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 95 to 145 (120v), 87 to 133 (110v), 83 to 121 (100v) |
Overvoltage correction | Voltage reduction of 12% applies when input is 127 to 145 (120v), 116 to 133 (110v), 111 to 121 (100v) |
Undervoltage correction | Voltage boost of 14% applies when input is 95 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v) |
LEDS ALARMS & SWITCHES | |
LED Indicators | Status LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for load and battery charge level |
Site wiring fault indication | Rear panel site wiring fault LED |
Alarms | Audible alarm indicates power failure and overload conditions |
Alarm cancel operation | Power-fail alarm can be silenced using alarm-cancel switch |
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support nominal voltage selection |
SURGE / NOISE SUPPRESSION | |
UPS AC suppression joule rating | 690 |
UPS AC suppression response time | Instantaneous |
UPS Dataline suppression | 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
EMI / RFI AC noise suppression | Yes |
PHYSICAL | |
Installation form factors supported with included accessories | Tower |
Primary form factor | Tower |
UPS / Power Module dimensions in primary form factor (height x width x depth / inches) | 10.2 x 6.8 x 13.2 |
UPS / Power Module dimensions in primary form factor (height x width x depth / cm) | 26 x 17.1 x 33.7 |
UPS / Power Module weight (lbs) | 45 |
UPS / Power Module weight (kg) | 20.4 |
UPS Shipping dimensions (height x width x depth / inches) | 14 x 9.8 x 18.5 |
UPS Shipping dimensions (height x width x depth / cm) | 35.6 x 24.8 x 47 |
Shipping weight (lbs) | 49.2 |
Shipping weight (kg) | 22.3 |
Cooling method | Fan |
UPS housing material | Steel |
ENVIRONMENTAL | |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity | 0 to 95%, non-condensing |
AC mode BTU / hr. (full load) | 161.1 |
Battery mode BTU / hr. (full load) | 498.1 |
AC mode efficiency rating (100% load) | 95% |
Audible Noise | Audible Noise < 50 dBA at Front Side 1 Meter |
COMMUNICATIONS | |
Communications interface | USB; DB9 Serial; Slot for SNMP/Web interface |
Network monitoring port description | Supports detailed monitoring of UPS and site power conditions |
PowerAlert software | Included |
Communications cable | USB and DB9 cabling included |
WatchDog compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
LINE / BATTERY TRANSFER | |
Transfer time | 4-6 milliseconds |
Low voltage transfer to battery power (setpoint) | 95V (120V), 87V (110V), 83V (100V) |
High voltage transfer to battery power (setpoint) | 145V (120V), 133V (110V), 121V (100V) |
SPECIAL FEATURES | |
Cold Start (startup in battery mode during a power failure) | Cold-start operation supported |
High availability UPS features | Hot swappable batteries |
Green & high efficiency features | Greater than 95% efficiency - GREEN UPS |
CERTIFICATIONS | |
UPS Certifications | Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI) |
WARRANTY | |
Product Warranty Period (Worldwide) | 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty. |