Done shopping? You can create a PDF of your cart for later or for your purchasing dept! Details at checkout.
Hear What Our Customers Are Saying
-
20+ Years Experience Helping IT Heroes
Take advantage of 20+ years of expertise from a partner with available resources for large deployments, multi-site projects, and complex IT initiatives. We have the team to get the job done. -
Free Solution Design With White Glove Engineers
Solutions architects and project engineers will help you envision a successful outcome and give you personalized recommendations based on your unique needs. Free. Apply today. -
Configuration & Installation Services
Let us take care of configuring and installing your equipment so you can get back to business. Available nationwide. Apply today. -
Equipment Trade-In Program
Refreshing old hardware? Let us coordinate the recycling or destruction in an environmentally friendly and safe manner. As a bonus, working with us gives you access to specific trade-in discounts towards your network refresh. Apply today. -
Exclusive Incentives, Special Pricing, & Financing
After helping you build and validate your solution, we’ll include any applicable discounts, financing, and incentives applied to your project to guarantee you get the most value out of your IT investments through Hummingbird Networks. Apply today.
750VA UPS Smart Pro Rack/Tower Line-Interactive 6 outlet
Key Features
- Tripp Lite SMART750RM1U .75kVA / 750VA / 600 watt line interactive UPS
- 1U rack/tower compatible form factor
- NEMA 5-15P input; 6 5-15R output receptacles
- Installed depth of only 16.75 in. / 42.5cm
- Sine wave output in both AC and battery backup modes
- Line Interactive UPS provides Automatic Voltage Regulation / AVR to maintain 120V nominal output during brownouts to 83V and overvoltages to 147V without using battery power
- Full load efficiency rating of 99% saves energy and ensures cool operating temperatures
- Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual devices
- PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as UPS batteries become depleted
- Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250 SNMP-enabled UPS, PDU and other networking devices
- Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces
- HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
- Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
- 3 stage metered LEDs offer current monitoring and battery charge level
- Mains power and voltage regulation LEDs offer at-a-glance power status information
- Front panel switches support self-test and alarm cancel functions
- Field replaceable, hot-swappable internal UPS batteries
Package Includes
- SMART750RM1U UPS System
- Mounting hardware
- Cabling for USB & DB9 monitoring and EPO switching
- PowerAlert unattended shutdown and UPS/Power monitoring software
- Instruction manual
OUTPUT | |
Output Volt Amp Capacity (VA) | 750 |
Output Watt Capacity (watts) | 600 |
Output power factor | 0.8 |
Nominal Output Voltage(s) Supported | 120V |
Frequency compatibility | 60 Hz |
Output voltage regulation (line mode) | -21%, +8% |
Output voltage regulation (Battery mode) | +/- 5% |
Built-in UPS output receptacles | 6 5-15R outlet(s) |
Built-in controllable switched load banks | Two switchable single-outlet 5-15R load banks |
Output AC waveform (AC mode) | Sine wave |
Output AC waveform (battery mode) | Pure Sine wave |
INPUT | |
Rated input current (at maximum load) | 7A |
Nominal Input Voltage(s) Supported | 120V AC |
UPS input connection type | 5-15P |
Input circuit breaker | 15A |
Recommended Electrical Service | 15A 120V |
Input cord length (ft.) | 10 |
Input cord length (m) | 3 |
Phase | Single-Phase |
BATTERY | |
Full load runtime (minutes) | 4.8 min. (600w) |
Half load runtime (minutes) | 16.2 min. (300w) |
DC system voltage (VDC) | 24 |
Battery recharge rate (included batteries) | Less than 4 hours from 10% to 90% |
Replacement battery cartridge (internal UPS battery replacement) | RBC64-1U |
Battery Access | Front panel battery access door |
Battery replacement description | Hot-swappable, user replaceable batteries |
VOLTAGE REGULATION | |
Voltage regulation description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147 |
Overvoltage correction | Input voltages between 128 and 147 are reduced by 12% |
Undervoltage correction | Input voltages between 83 and 107 are boosted by 14% |
LEDS ALARMS & SWITCHES | |
LED Indicators | 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
Alarms | Audible alarm indicates power-failure, overload and low-battery conditions |
Alarm cancel operation | Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status |
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation |
SURGE / NOISE SUPPRESSION | |
UPS AC suppression joule rating | 450 joules |
UPS AC suppression response time | Instantaneous |
EMI / RFI AC noise suppression | Yes |
PHYSICAL | |
Installation form factors supported with included accessories | 4 post 19 inch rackmount; 2 post 19 inch rackmount |
Primary form factor | Rackmount |
UPS / Power Module dimensions in primary form factor (height x width x depth / inches) | 1.7 x 17.5 x 16.8 |
UPS / Power Module dimensions in primary form factor (height x width x depth / cm) | 4.4 x 44.4 x 42.5 |
Rack Height | 1U |
UPS / Power Module weight (lbs) | 30 |
UPS / Power Module weight (kg) | 13.6 |
UPS Shipping dimensions (height x width x depth / inches) | 6.2 x 23.5 x 22.5 |
UPS Shipping dimensions (height x width x depth / cm) | 15.9 x 59.7 x 57.2 |
Shipping weight (lbs) | 34 |
Shipping weight (kg) | 15.4 |
Cooling method | Fan |
UPS housing material | Steel |
ENVIRONMENTAL | |
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity | 0 to 95%, non-condensing |
AC mode BTU / hr. (full load) | 39 |
AC mode efficiency rating (100% load) | 99% |
COMMUNICATIONS | |
Communications interface | USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network monitoring port description | Supports detailed monitoring of UPS and site power conditions |
PowerAlert software | Included |
Communications cable | USB and DB9 cabling included |
WatchDog compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
LINE / BATTERY TRANSFER | |
Transfer time | 5 milliseconds AC to DC; 1 millisecond DC to AC |
Low voltage transfer to battery power (setpoint) | 83 |
High voltage transfer to battery power (setpoint) | 147 |
SPECIAL FEATURES | |
Grounding lug | Back panel grounding lug |
Cold Start (startup in battery mode during a power failure) | Cold-start operation supported |
High availability UPS features | Hot swappable batteries |
Green & high efficiency features | Individually controllable load banks |
CERTIFICATIONS | |
UPS Certifications | Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI) |
WARRANTY | |
Product Warranty Period (Worldwide) | 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty. |
Connected Equipment Insurance (U.S., Canada & Puerto Rico) | $250,000 Ultimate Lifetime Insurance |